 Xserve (Late 2006/Early 2008)
073-1096 Rev. B
Processor Heat Sink
Replacement Instructions
Follow the instructions in this document carefully. Failure to follow these instructions could
damage your equipment and void its warranty.
Online instructions are available at http://www.apple.com/support/diy/.
Working Safely Inside the Xserve
Always touch the Xserve enclosure to discharge static electricity before you touch any
components inside the Xserve. To avoid generating static electricity, do not walk around the
room until you have nished working inside the server and have replaced the cover. To minimize
the possibility of damage due to static discharge, wear an antistatic wrist strap while you work
inside the Xserve.
Warning: Always shut down the Xserve and disconnect the power cords before opening
it to avoid damaging its internal components or the components you are installing. Don’t
open the server while it is turned on. Even after you shut down the Xserve, its internal
components can be very hot. Let it cool before you open it.
Tools Required
The following tools are required for this procedure:
Phillips #1 screwdriver
Antistatic wrist strap (if available)
Alcohol wipe for cleaning processor (supplied with the part)
Thermal grease syringe for replacing thermal grease on processor (supplied with the part)
Removing the Xserve from a Rack
Alert users that the server will be unavailable for a period of time. 1.
Shut down the Xserve (see the Xserve User’s Guide for help) and then wait to let the Xserve 2.
internal components cool.
Zobrazit stránku 0
1 2 3 4 5 6 ... 13 14

Shrnutí obsahu

Strany 1 - Processor Heat Sink

 Xserve (Late 2006/Early 2008)073-1096 Rev. BProcessor Heat SinkReplacement InstructionsFollow the instructions in this document carefully. Failure t

Strany 2 - Thumbscrews

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 10Use the edge of the package that the alcohol wipe came in as a spatula t

Strany 3 - Opening the Xserve

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 11Note: When installing the processor on the logic board, align the proces

Strany 4

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 12Carefully seat the heat sink over the processor, aligning the four screw

Strany 5

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 13Ensure the airow duct ts ush all over, and does not protrude above th

Strany 6

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 14 Apple Inc.© 2006, 2008 Apple Inc. All rights reserved.Under the copyri

Strany 7

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 2Warning: Always shut down the Xserve before opening it to avoid damaging

Strany 8

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 3Opening the XserveLoosen the thumbscrews at the back of the top cover and

Strany 9

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 4Caution: Try not to completely remove the screws from the airow duct. Ti

Strany 10

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 5Loosen the four screws securing the heat sink in the order indicated belo

Strany 11

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 6Caution: Whenever you handle the heat sink, handle it from the slotted si

Strany 12 - Replacing the Airow Duct

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 7Caution: Each heat sink is connected to the logic board by a small 2-pin

Strany 13 - Closing the Xserve

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 8Installing the Replacement Processor Heat SinkNote: The thermal bond betw

Strany 14

Xserve (Late 2006/Early 2008) Processor Heat Sink Replacement Instructions 9Clean o any existing thermal grease on the top face of the processor usi